Air Showers offer an effective way to reduce contaminants carried by individuals entering or leaving a controlled area. The Air Shower can be the solution to many contamination problems.

Air Shower Tunnels are protected passageways that allow large quantities of personnel to pass into controlled areas.

Air Showers and Tunnels supply concentrated CLASS 100 sterile air flows to remove contamination while an individual stands in or walks through a specially constructed air chamber. Pressurized air streams from nozzles at a velocity ranging from 6,000 to 10,000 feet per minute. This ensures the efficient scrubbing action necessary for the removal of particulate matter. Contaminated air is directed downward through the grilles and hollow walls of the Air Shower to the filter. Particles as small as 0.3 microns are removed with 99.99% efficiency.

ATMOS-TECH Air Shower Tunnels are used as downflow booths to remove particulate contamination from personnel entering clean rooms and sterile rooms. The Air Shower Tunnel is designed as a combination of basic floor plan styles placed either side by side or end to end. Air Showers and Tunnels meet all federal, military and industrial specifications for use with life science, bio medical, pharmaceutical, parental drug, microelectronic, aerospace, precision manufacturing and other applications. All Air Showers and Air Shower Tunnels manufactured by Atmos-Tech are warranted for a period of one year from the date of delivery.

Atmos-Tech Air Showers and Air Shower Tunnels are economical to operate and require minimal maintenance.

HFC Model for HEPA Filter Ceiling Model add 6" to base section height.

Special Sizes are available upon request.

Unit of Measure

Specifications

Base Section Height

N/A 90 in

Width

N/A 52 in

Length

N/A 44 in

Blower Box Height

N/A 26 in

Door Width

N/A 36 in

Width ID

N/A 39 1/2 in

Length ID Clear

N/A 35 in

Number of Nozzles

N/A 20 in

Quantity of Blowers

N/A 1

CFM/Blower @ 2" WG

N/A 1010

Speed

N/A 3600 rpm

Wheel Diameter

N/A 12 1/2 in

3 Door Available

N/A No

Shipping Weight

N/A 1600

Filter 11 1/2 Deep

N/A 18 x 24 in

Power

N/A 2 hp

Motor

N/A 3N667

Blower

N/A 4C329
Voltage1 N/A 208 V230 V460 V

Current

N/A 3.3 A6.6 A7.0 A

Special Atmos-Tech Air Shower Features

Special Atmos-Tech Air Shower Features

N/A
  • Light switch, audible alarm and alarm reset
  • Four-line, 64-character alpha/numerical LCD display which monitors system function during normal operation and displays menu functions for service and system key changes.
  • Sixteen Key membrane keypad for system operation
    -Four number code to turn control on and off
    -Four number code to access system set-up
  • Microprocessor Programming Capabilities
    -Time of day
    -Day of the week
    -Cycle time
    -Delay unlock time
    -Designate entry and exit doors
    -Replace entry system four-digit code
    -Initiate time-lock feature
    -Initiate security locking feature with a four-digit code
    -Initiate single direction access feature
  • Microprocessor Diagnostic Capabilities
    -Air Shower disabling feature
    -Blower operations check
    -Door switch operations check
    -Door lock operations check
    -Presence sensor/mat switch check
    -Record blower operating hours
    -Record Air Shower cycle
  • Standard interlocking doors which release automatically with power failure
  • Standard fluorescent lighting contained in the ceiling to reduce turbulence
  • Optional HEPA Ceiling provides a constant laminar flow to increase protection of the area
  • Optional Ion Bar static eliminators when required
  • Safety feature which automatically releases door locks in the event of a power failure
  • Emergency stop button on each Air Shower which releases locks for exiting while sounding an alarm.

Standard Air Shower Components

Standard Air Shower Components

N/A
  • Motor/Blower assembly
  • Power control box
  • Emergency release button
  • HEPA filter 99.7% effective on 0.3 micron particles
  • Adjustable nozzles
  • Fluorescent light fixture
  • Automatically activated floor switch
  • Anodized aluminum doors with plexiglass
  • Microprocessor control panel
  • Access panels for easy maintenance
  • Electric interlocking chamber
  • Single connection junction box
  • Construction: High-Density 7/8" particle board laminated with plastic [Formica or equivalent]
  • In accordance with our policy of continual product improvement, ATMOS-TECH reserves the right to incorporate and use equipment and material to conform with the latest design of its products while maintaining the specifications of the equipment.

Optional Equipment

Optional Equipment

N/A Aluminum grated floor with clean-out pan Ceiling-mounted HEPA filter which provides a constant laminar flow for added protection Epoxy Painted cold rolled steel and stainless steel Explosion-proof construction Ion bar static eliminators Knock-down assembly Magnehelic gauge HEPA and pre-filter Magnehelic gauges with alarms Raised floor return Safety plate glass doors Side-mounted HEPA and motor/blower Water misting systems
  • 1 Other voltages available upon request.